Brand Name :YONGDE
Model Number :YH10W5-9
Certification :ISO9001/KEMA
Place of Origin :Zhejiang,China(Mainland)
MOQ :1pcs
Price :negotiation
Payment Terms :T/T or western Union or L/C or PayPal
Supply Ability :30,000pcs per month
Delivery Time :21days per container
Packaging Details :carton
Model :YH10W5-9
Material :Silicon Rubber
Rated voltage :9KV
Accessory :Bracket,Insulating cap,Cooper lead,Insulator,Hoop
Purpose :Over-Voltage Protection
Structure :Self-Standing
Color :Customized
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

3 Phase Polymeric Lightning Surge Diverter for Transmission Line

Description:

Polymeric Surge Arresters can be applied to a variety of systems including substation equipment, AC-DC converters, railway power system and power distribution units ranging from 0.25kV to 765kV systems. These surge arresters demonstrate excellent protection properties.

Applications:

1. Distribution networks

2. Transmission line

3. Substation

4. Railway power station

5. Alternator and electromotor

Specifications:

Type YH10W5-9/24
Rated voltage---------kV 9
MOCV ----------------kV 7.65
Nominal Current-------kV 10
Residual voltage of steep impulse----at 5kA(kV) 26.7
8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) 24.7
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) 18.7
1mA D.C reference voltage (kV) 12.7
Line discharge level 1
2mS long duration impulse current A 400
4/10µS High current impulse kA 100
Lightning impulse withstand kV 95
Power frequency voltage withstand(dry/wet)kV 28
0.1S TOV--------------kV 10.8
1S TOV----------------kV 10.35
10S TOV---------------kV 9.9
1200S TOV-------------kV 9
Creepage distance ----mm 338
Material employed in series non-linear resistor Zinc Oxide

Working condition:

1) Environment temperature: -40--+40 degree
2) altitude: <1000m
3) 48HZ

4) Power frequency voltage should not be more than continuous running voltag
5) Max wind speed should be less than 35m/s
6) Earthquake intensity should be less than 7 degree
7) If used in contamination area, should be noted in advance.