Hangzhou Yongde Electric Appliances Co.,Ltd

Superior Quality, Superior Service!

Manufacturer from China
Verified Supplier
9 Years
Home / Products / Metal Oxide Surge Arrester /

Polymeric Metal Oxide Surge Arrester for Substation / AC - DC Converters / Power Distribution Units

Contact Now
Hangzhou Yongde Electric Appliances Co.,Ltd
Visit Website
City:hangzhou
Province/State:zhejiang
Country/Region:china
Contact Person:MrMatt
Contact Now

Polymeric Metal Oxide Surge Arrester for Substation / AC - DC Converters / Power Distribution Units

Ask Latest Price
Video Channel
Brand Name :YONGDE
Model Number :YH5W5-24
Certification :ISO9001/KEMA
Place of Origin :Zhejiang,China(Mainland)
MOQ :1pcs
Price :negotiation
Payment Terms :T/T or western Union or L/C or PayPal
Supply Ability :30,000pcs per month
Delivery Time :21days per container
Packaging Details :carton
Type :Surge Arrester
Material :Silicon Rubber
Accessory :Bracket,Insulating cap,Cooper lead,Insulator,Hoop
Purpose :Over-Voltage Protection
Structure :Self-Standing
Color :Customized
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Polymeric Metal Oxide Surge Protector , Station Metal Oxide Lightning Protector

Description:

YongDe Surge Arresters can be applied to a variety of systems including substation equipment, AC-DC converters, railway power system and power distribution units ranging from 0.25kV to 765kV systems. These surge arresters demonstrate excellent protection properties. YongDe surge arresters incorporate YNR elements (YongDe Non-linear Resistor ZnO Elements) with superior non-linear voltage-current characteristics, high quality and reliability. Metal oxide type surge arresters offer such special features inherent in the gap-less structure, such as a quick response to surge voltage, high energy dissipation capability, safe operation, compactness / lightweight and freedom from pollution.

Features:

1. Compact and Lightweight

2. Extremely Safe Pressure Relief Performance

3. Superior Performance against Environmental Contamination

4. Directly Molded Structure

5. Compliance with International Standards(IEC60099-4)

6. Simple Support Structure

7. Manufactured at Advanced ISO-9001 certified facilities

Specifications:

Type YH5W5-24/64.3
Rated voltage---------kV 24
MOCV ----------------kV 19.5
Nominal Current-------kV 5
Residual voltage of steep impulse----at 5kA(kV) 69.5
8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) 64.3
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) /
1mA D.C reference voltage (kV) 34
Line discharge level 1
2mS long duration impulse current A 250
4/10µS High current impulse kA 65
Lightning impulse withstand kV 125
Power frequency voltage withstand(dry/wet)kV 50
0.1S TOV--------------kV 28.8
1S TOV----------------kV 27.6
10S TOV---------------kV 26.4
1200S TOV-------------kV 24
Creepage distance ----mm 824
Material employed in series non-linear resistor Zinc Oxide
Inquiry Cart 0